Purchasing Office in USA!

For USA brands, Direct shipping from USA to worldwide destination!
Product Detail
AEMC L452 - 2-Channel Data Logger with LCD, Event and Pulse, DataView Software
Category:
▶ AEMC
keyWord:
AEMC L452 - 2-Channel Data Logger with LCD, Event and Pulse, DataView Software
Describe:
AEMC L452
Contact us
Description
http://www.jinstartech.com/
General Attributes:
AEMC L452 very good price
Data Logger Model L452 (2-Channel, w/LCD, 100mV/1V/10VDC, 4 to 20mADC, Event and Pulse, DataView Software)
- Current and Voltage data logger (4-20mA, ±100mV, ±1V, ±10V) user selectable
- Event counter, dry contact closure and logical level (pulse) detection
- Real-time display of measurements
- Includes FREE DataView® software for data storage, real-time display, analysis & report generation
- Wireless Bluetooth communication
- Applications
- Determine machinery run or down times
- Determine event sequencing
- Count events and records
- Record event duration
Description
- Current and Voltage data logger (4-20mA, ±100mV, ±1V, ±10V) user selectable
- Event counter, dry contact closure and logical level (pulse) detection
- Real-time display of measurements
- Includes FREE DataView® software for data storage, real-time display, analysis & report generation
- Wireless Bluetooth communication
2-Channel Data Logger (100mV/1v/10VDC) with LCD, Event and Pulse, DataView Software
The L452 can log DC voltage, DC current, 4 to 20mA pulse counts, or events, using either one or two independent inputs. The L452 features an onboard menu-based interface for navigating measurement data and selecting configuration options. This Control Panel also enables users to change settings on the instrument, view real-time measurements, schedule recording sessions, and perform other configuration tasks.
Two-Channel DC Voltage, Current, Pulse & Event
The Model L452 is a low-cost, simple-to-use, two-channel data logger. It records DC voltage, DC current, pulses and events. Its two input channels allow the user to connect to various types of sensors in order to record data such as pressure, temperature, flow, humidity and more. This logger can also be used to record events such as machine run time. Each channel's real-time measurement is displayed on the LCD screen.
The L452 communicates via USB or Bluetooth for configuration and data transfer to a PC. The unit can also be configured using its front panel with a very simple user interface. The menus are multilingual. Users can lock the keypad within the DataView software. Alarms can be set on various measurements. DataView software for data storage, real-time display, analysis, and report generation from a pre-defined or custom template is included. Its ergonomics make it simple to use. It has a magnetized rear panel or optional wall mount holster and desktop stand which facilitate mounting. The L452 operates on rechargeable batteries or can be powered from a USB cable.
Manufacturer Specs
ELECTRICAL | ||||
Channels | Two | |||
Input | Six-pin terminal strip | |||
Measurements | DC Current | DC Voltage | Event | Pulse |
Range | 4 to 20mA | 100mV, 1V, 10V | N/A | N/A |
Accuracy (% of Reading) | ±(0.25% + 5cts) | ±(0.5% + 1cts) | N/A | N/A |
Resolution | 0.01mA | 0.1mV, 1mV, 10mV | N/A | N/A |
Input Impedance | 100Ω | 1MΩ | 1MΩ | N/A |
Sample Period | DC inputs: 200, 400, 600, or 800ms; or from 1 to 60 seconds Pulse detection: 10ms |
|||
Storage Modes | Start/Stop (ends when memory is full or when the recording stop time is reached, whichever comes first) | |||
Recording Length | 10 minutes to 1 year, set via instrument front panel or through DataView® | |||
Memory | 32MB internal Flash memory (up to 1024 logging sessions, 16M samples) | |||
Communication | Bluetooth 2.1, Class 1 or USB 2.0 | |||
Power Source | External: via USB connector Internal: 2 x AA NIMH rechargeable batteries (charges through USB port) |
|||
Battery Life | Up to 180 days (dependent on storage rate/recording length) | |||
MECHANICAL | ||||
Dimensions | 1.275 x 2.578 x 5.413" (32.4 x 65.5 x 137.5mm) | |||
Weight (with battery) | 190g (6.7oz) with batteries | |||
Vibration | IEC 68-2-6 (1.5mm, 10 to 55Hz) | |||
Shock | IEC 68-2-27 (30G) | |||
ENVIRONMENTAL | ||||
Operating Temperature | 32 to 122°F (0 to 50°C) | |||
Humidity | 16 to 85% | |||
Protection | IP 40 (instrument alone); IP 20 (instrument with terminal strip) |